Technical Information
|
Type
|
2400-A16
|
Inputs 1~16 Specifications: |
Analogue or Digital. |
Inputs 1~16 Analogue Specifications: |
16 Individually Isolated Universal or Non-Isolated RTD Analogue Inputs. |
Input Resolution |
16 Bits, 50,000 Steps Average (some ranges may differ). |
Input Isolation |
2500Vac for 1 minute between All Input Channels. |
Voltage Input Specifications:
|
Input Impedance |
>500KΩ on all ranges. |
mV Maximum Over-range |
3Vdc Continuous. |
V Maximum Over-range |
24Vdc Continuous. |
mV Range |
-200~200mV. |
V Range |
0~1V, 0~15V. |
Accuracy |
0.1% FSO Max. |
Linearity and Repeatability |
0.1% FSO Max. |
Channel Separation |
0.001% Max. |
Ambient Drift |
0.003%/°C FSO Typical. |
Noise Immunity (CMRR) |
160dB Tested @ 300Vrms 50Hz. |
RF Immunity |
1% effect FSO Typical. |
Current Input Specifications:
|
Minimum Recommended |
Span 0~1mA (gives 1000 steps on output). |
Input Impedance |
45Ω. |
Maximum Over-range |
Protected by PTC Up to 24Vdc Max. |
mA Range |
0~20mA (4~20mA). |
Accuracy |
0.1% FSO Max. |
Linearity and Repeatability |
0.1% FSO Max. |
Channel Separation |
0.001% Max. |
Ambient Drift |
0.003%/°C FSO Typical. |
Noise Immunity (CMRR) |
160dB Tested @ 300Vrms 50Hz. |
RF Immunity |
1% effect FSO Typical. |
Thermocouple (T/C) Input Specifications:
|
Thermocouple Types |
B, E, J, K, N, R, S, T. |
Input Impedance |
>500KΩ. |
T/C Lead Resistance |
100Ω Max. |
Cold Junction Compensation. |
-10~60°C. |
CJC Drift |
0.02°C/°C For Installation Upright. |
Accuracy |
0.1% of FSO ±1°C Typical. |
Sensor Fail |
Upscale or Downscale Selectable (Upscale Default). |
Type B Range |
0~1800°C (30~3270°F). |
Type E Range |
-200~800°C (-320~1470°F). |
Type J Range |
-200~1000°C (-320~1830°F). |
Type K Range |
-200~1300°C (-320~2370°F). |
Type N Range |
-200~1300°C (-320~2370°F). |
Type R Range |
0~1700°C (30~3090°F). |
Type S Range |
0~1700°C (30~3090°F). |
Type T Range |
-200~400°C (-320~750°F). |
RTD Input Specifications:
|
Pt100 RTD Type |
3 Wire Pt100 RTD DIN 43760:1980 Standard Input. |
Pt1000 RTD Type |
3 Wire Pt1000 RTD Standard Input. |
Sensor Current |
0.6mA Continuous. |
Lead Wire Resistance |
Pt100: 10Ω/wire Max. Pt1000: 5Ω/wire Max. 0.1% FSO Offset Error per Ω of Lead Resistance. |
Sensor Fail |
Upscale or Downscale Selectable (Upscale Default). |
Ambient Drift |
0.003°C/°C Typical. |
Accuracy |
0~300°C ±0.1°C. 0~850°C ±0.3°C, Isolated Channels Only. |
Resolution |
0.01°C for -200~250°C, (-140~210°F). 0.1°C for -200~850°C (-320~1560°F), Isolated Channels Only. |
Inputs 1~16 Pulses & Frequency: |
Meter Pulses, Frequency, Counter or On/Off State Inputs. |
Input Type |
Clean Contact, Open Contact - NPN, PNP. |
Accuracy |
±0.5%. |
Frequency Range |
0~2500Hz. |
Frequency Resolution |
0.1Hz. |
Fast Counter Range |
0~2500Hz. |
Maximum Amplitude |
0~5Vdc |
Debounce |
0~50Hz Max. |
Counter Register Output |
32bit. |
Dedicated Digital Input 1~4 Specifications: |
4 Opto Isolated Digital Inputs with LED Indication On Each Input. |
Applications |
Meter Pulses, Frequency, Counter or On/Off State Inputs. |
Functions |
Up Count On Each Pulse. |
Input Voltage |
5~30Vdc. |
Threshold |
4.6V typical. |
Load @ 5V |
1.1mA per Channel. |
Load @ 24Vdc |
7.0mA per Channel. |
Counter Register Output |
32bit. |
Frequency Range |
0~8000Hz. |
Frequency Debounce |
5msec. |
Debounce Counter Range |
0~100Hz. |
2400-A16 Output Specifications.
|
Dual Analogue Outputs Source: |
2 Isolated Analogue Outputs (not isolated from each other). |
mA Range |
4~20mA Only. |
Resolution |
12bit, 4096 steps. |
Output Drive |
500Ω Max @ 24V Supply. |
Relay Outputs: |
2 Isolated Relays with LED Indication On Each Output. |
Functions |
2 on Board Controllers (16 with 2400-R2), can be used as Set Point (SV), Switching Differential, Auto/Manual, Manual Output Setting, Dual Action Control, Single Action Control, Heat/Cool, Cool Only, Heat Only. |
Contact Material |
Gold Clad Silver. |
Relay Ratings |
30Vdc, 3A Max. |
Approved to Standard |
UL. |
2400-A16 General Specifications.
|
Comms Ports: |
|
Port 1 |
RS422/RS485. |
Port 2 |
RS232/RS485. |
Ethernet TCP/IP Port (optional) |
Lantronix XPort® (Replaces Comms Port 1). |
Data Rate |
9600 (MicroScan), 19200, 57600 or 115200 baud. |
Parity bit |
Even or None (MicroScan). |
Protocols |
ASCII. Std (MicroScan), Modbus RTU/TCP Auto Detect. |
Power Options: |
10VA. |
Factory Set: H |
85~265Vac, 95~370Vdc. |
Factory Set: M |
24~48Vac, 17~72Vdc. |
Factory Set: L |
10~30Vdc (recommend 1A power supply). |
Safety Compliance:
|
EMC Emissions |
EN55022-A. |
EMC Immunity |
EN50082-1. |
Safety |
EN60950. |
Mains isolation |
250Vac. |
Isolation test voltages: |
|
Mains to output |
3000Vac, 50Hz. |
Mains to earth |
1500Vac, 50Hz. |
General Specifications:
|
Accurate to |
≤ ±0.1%/°C FSO typical. |
Linear Repeatability |
≤ ±0.1%/°C FSO typical. |
Ambient drift |
≤ ±0.01%/°C FSO typical. |
Isolation Test Voltages |
Between Input and Output: 3750Vac for 1min. |
Response Time |
400msec Typical (10~90% 300msec Typical). |
Noise Immunity |
125dB CMRR Average (2.0kVdc Limit). |
RF immunity |
< 1% effect FSO typical. |
Operating temperature |
0~60°C. |
Storage temperature |
-20~80°C. |
Operating humidity |
5~85% RH max. |
Housing: |
Material ABS Inflammability V0 (UL94). |
Mounting |
35mm symmetrical DIN rail. |
Dimensions |
L=255, W=145, H=60mm. |
Weight |
0.9kg Includes Packaging. |