intech-xid-l-loop-powered-isolators
 
Search
Menu Close

Intech XID-L - Loop Powered Isolators

Isolating 4~20mA Input to 4~20mA Output Loop Powered Transmitter. 12.5mm Wide!
Part Number: XID-L1, XID-L2, XID-L4
Manufacturer:
0Types Available
Back to Previous Page

Features:

  • Input to Output Isolation 300Vac.
  • High Accuracy 0.03%.
  • Reverse Polarity Protected.
  • Compact DIN Rail Mount Enclosure.
  • Available with 1, 2 or 4 Transmitters per Enclosure.
  • Easy to Install.
  • Low Cost.

Ordering Information:

XID-L1
XID-L2
XID-L4
One Loop per Enclosure.
Two Loops per Enclosure.
Four Loops per Enclosure.

 

Dual Output Signal Isolators:

Use the XID-L2 dual channel model. Wire the 4~20mA input in series through both inputs on the transmitter, and the 2 outputs are totally isolated. The outputs are loop powered so you need a separate 24Vdc power supply for each channel.

XID-L Specifications.

Input  4~20mA (up to 4 channels).
Input  Resistance 50Ω.
Output  2 wire 4~20mA (Loop Powered).
Output Load Resistance  875Ω @ 24Vdc. (50Ω/V above 6.5Vdc.)
Power Supply  24Vdc Nominal (28Vdc Max). 
Input Voltage Protection 30Vdc. 
EMC Emissions Compliance  EN 61326-1.
Safety Compliance   EN 61010-1.
Accurate to   <±0.03% of span typical.
Linearity & Repeatability   <±0.03% of span typical.
Ambient Drift   <±0.01%/°C of span typical.
R.F. Immunity   <0.5% Effect of span typical.
Isolation Test Voltages Between Input and Output:  300Vac.
 Between the separate XID-L transmitters:  300Vac.
Response Time  <2msec (From 0~90%, 100~10%).
Operating Temperature  -20~70°C.
Storage Temperature  -20~85°C.
Operating Humidity  5~85%RH Max. Non-Condensing.
Mounting   35mm Symmetrical Mounting Rail.
Dimensions   H=90, W=12.5, D=112mm. 

Features:

  • Input to Output Isolation 300Vac.
  • High Accuracy 0.03%.
  • Reverse Polarity Protected.
  • Compact DIN Rail Mount Enclosure.
  • Available with 1, 2 or 4 Transmitters per Enclosure.
  • Easy to Install.
  • Low Cost.

Ordering Information:

XID-L1
XID-L2
XID-L4
One Loop per Enclosure.
Two Loops per Enclosure.
Four Loops per Enclosure.

 

Dual Output Signal Isolators:

Use the XID-L2 dual channel model. Wire the 4~20mA input in series through both inputs on the transmitter, and the 2 outputs are totally isolated. The outputs are loop powered so you need a separate 24Vdc power supply for each channel.

$294.00 ex GST
i h
$526.00 ex GST
i h
$806.00 ex GST
i h