Search
Menu Close

Procon PT8AIVS - 8 Voltage Input Module Fully Isolated (TCP)

Manufacturer:
The PT8AIVS is a 8 channel voltage input module. The inputs are fully isolated from input to logic and between inputs. This module is ideal for monitoring voltages which are isolated from each other and cannot be connected to a common point of reference.
Part Number: PT8AIVS
Back to Previous Page
Product Files
$422.00 ex GST
i h

The PT8AIVS is a 8 channel voltage input module. The inputs are fully isolated from input to logic and between inputs. This module is ideal for monitoring voltages which are isolated from each other and cannot be connected to a common point of reference.

The standard setting for the PT8AIVS module is 0 – 10V. An input voltage of 0 – 10Volts represents an output of 0 – 4095 and 2 volts would give a reading of 819 ± 1LSB. To obtain an output value of 0 to 4095 for an input signal of 2 to 10V the offset switch is switched on. This module can also be configured for a 0 – 10.000V input range or +/- 10.000V input.


PROMUX TCP (TCP/IP I/O Modules)

PROMUX TCP is an innovative modular I/O system which provides a simple solution for distributed I/O requirements.

The PROMUX TCP system consists of stand-alone Digital and Analog Input and Output modules which are connected together on an ETHERNET 10/100Base-T network using the MODBUS TCP protocol.

The PROMUX TCP modules also have built in web servers. This enables configuration and diagnostic data to be accessed via a standard web browser.

All PROMUX TCP modules plug directly onto an industry standard DIN rail. All modules have isolation between the field and logic.

Technical Information

Analog Inputs 8
Type Differential
Voltage 0(2)-10Vdc
Resolution 16 bit
Sample rate 0.71 samples/sec
Input Impedance 110Kohms
Isolation (Inter Channel) 350VAC (Pk-Pk)
Drift 100 ppm/deg.C typ.
Accuracy 0.2 % of span
Isolation (Field & Logic) 1500VAC RMS

The PT8AIVS is a 8 channel voltage input module. The inputs are fully isolated from input to logic and between inputs. This module is ideal for monitoring voltages which are isolated from each other and cannot be connected to a common point of reference.

The standard setting for the PT8AIVS module is 0 – 10V. An input voltage of 0 – 10Volts represents an output of 0 – 4095 and 2 volts would give a reading of 819 ± 1LSB. To obtain an output value of 0 to 4095 for an input signal of 2 to 10V the offset switch is switched on. This module can also be configured for a 0 – 10.000V input range or +/- 10.000V input.


PROMUX TCP (TCP/IP I/O Modules)

PROMUX TCP is an innovative modular I/O system which provides a simple solution for distributed I/O requirements.

The PROMUX TCP system consists of stand-alone Digital and Analog Input and Output modules which are connected together on an ETHERNET 10/100Base-T network using the MODBUS TCP protocol.

The PROMUX TCP modules also have built in web servers. This enables configuration and diagnostic data to be accessed via a standard web browser.