Manufacturer:
The Si-CA 030 offers everything heating engineers need to inspect and maintain residential and commercial boilers, with wireless connection to our smartphone app and automatic generation of servicing reports and certificates.
Part Number: Si-CA 030
Back to Previous Page
Call for pricing
Delivery date: 3-4 weeks

Residential & commercial combustion analyser The latest in combustion analysis technology

Compact, Light and Durable Design


✔ Up to three gas sensors O2, CO and NO (for NOx)
✔ CO sensor measurement up to 8,000 ppm
✔ Auto pump cut-off for high CO levels
✔ Color display screen
✔ Lightweight, only 350 g (12 oz)
✔ Data management with automatic logging & report creation


Key features:

  • Predictive maintenance with estimated sensor life & calibration reminders
  • Draft & differential pressure measurements
  • Calculated CO2% value
  • NOx capable with NO sensor 
  • Quick and easy pump On/Off control
  • Combustion efficiency & excess air calculations
  • CO safety monitoring in ambient air
  • Protective rubber holster
  • Extended warranties available


General Features

Dimensions 19.4 x 9.9 x 4.9 cm (7.5 x 3.5 x 4.9’’)
Weight 350 g (12 oz)
Display Color display screen; Size: 320 x 240 pixels
Keypad 5 keys
Material ABS-PC
Protection IP42
Connection - Wireless: class 2 range, range frequency from 2402 MHz to 2480 MHz with a transmit power of 1 dBm. Range up to 15 m (50 ft), depending on smartphone radio strength. Minimum required versions: Android 8.0, iOS 12.4, BLE 4.0 Low Energy - USB
Power supply Rechargeable battery, USB power supply Li-Ion 5100 mA/h 3.6 V battery / Power supply voltage of the mains unit: 100-240 Vac, 50-60 Hz Mains unit: 5 Vdc/2A

Battery

Battery life > 8 h; Charging time: Fully charge: < 6.5 h; 50%: < 2.5 h
Environmental conditions of use

Temperature: from -5 to 45 °C (23 to 113 °F),

Hygrometry: in non-condensing conditions (< 85% RH)

Maximum altitude: 2000 m (6561’)

Storage temperature From -20 to 50 °C (-4 to 122 °F)
Languages English, French, German, Spanish, Italian, Portuguese
European Union Directives 2014/53/EU (RED); 2015/863 EU (RoHS 3)
Regulations EN 50379-1 and EN 50379-2; UNI 10389; UL & cUL Certification; BS 7967:2015; BS EN 50543:2011; UNE 60670-10; ES.02173.ES

Technical Information

Parameter

Sensor

Measuring range

Resolution

Accuracy(1)

T90 response time

O2 Electrochemical 0 to 25% 0.01% ±0.2% vol

< 30 s

CO Electrochemical 0 to 8000 ppm 1 ppm

±8 ppm < 160 ppm

±5% rdg up to 2000 ppm

±10% rdg > 2000 ppm

< 40 s
CO2 Calculated 0 to 99.9% 0.1% -

-

NO (optional) Electrochemical 0 to 5000 ppm 1 ppm

±5 ppm < 100 ppm

±5% rdg > 100 ppm

< 40 s
NOx (optional) Calculated 0 to 7500 ppm 1 ppm - -
Flue temperature TcK

-20 to +1250 °C

-4 to +2282 °F

0.1 °C

0.1 °F

±2 °C or ±0.5% rdg(2)

±3.6 °F or ±0.5% rdg(2)

-
Air temperature NTC or TcK -20

-20 to +120 °C

-4 to +248 °F

0.1 °C

0.1 °F

±2 °C

±3.6 °F

-
Differential temperature Calculated

0 to 1250 °C

0 to 2282 °F

0.1 °C

0.1 °F

- -
Pressure/Draft Semiconductor

-200 to +200 mbar

-80 to +80 inH2O

0.01 mbar

0.001 inH2O

±1% rdg ±0.03 mbar

±1% rdg ±0.012 inH2O

-
Excess air Calculated 0 to 999% 1% - -
Efficiency Calculated 0 to 100% (Gross/HHV(3)) 0.1% - -
Efficiency (condensation) Calculated 0 to 125% (Net/LHV(4)) 0.1% - -

Sauermann Combustion App

The Sauermann Combustion app lets you control your Si-CA analyzer remotely, view measurement results in real time, and customise them before exporting in the format of your choice.



✔ Fast, easy wireless connection
✔ Remote live view of combustion analysis data as list or graph
✔ Remote control to change settings
✔ Data saving, including automatic logging
✔ Report creation in PDF, CSV (for Excel) and XML formats
✔ Databases for customers, operators, & equipment



Scan the QR code below to download the app today:




Sauermann Combustion Software (Si-CA 130 & Si-CA 230 ONLY)


The Sauermann Combustion software lets you control your Si-CA 130 and Si-CA 230 analyzers remotely, view measurement results in real time, and customise them before exporting in the format of your choice


  • Remote live view of combustion analysis data as list or graph
  • Remote control to change settings
  • Data saving, including automatic logging
  • Report creation in PDF, CSV (for Excel) and XML formats
  • Databases for customers, operators, & equipment


Download the Software from the Sauermann website here >>

Residential & commercial combustion analyser The latest in combustion analysis technology

Compact, Light and Durable Design


✔ Up to three gas sensors O2, CO and NO (for NOx)
✔ CO sensor measurement up to 8,000 ppm
✔ Auto pump cut-off for high CO levels
✔ Color display screen
✔ Lightweight, only 350 g (12 oz)
✔ Data management with automatic logging & report creation


Key features:

  • Predictive maintenance with estimated sensor life & calibration reminders
  • Draft & differential pressure measurements
  • Calculated CO2% value
  • NOx capable with NO sensor 
  • Quick and easy pump On/Off control
  • Combustion efficiency & excess air calculations
  • CO safety monitoring in ambient air
  • Protective rubber holster
  • Extended warranties available