CCS ACTL-1250 Series Split-Core Current Transformers 250A to 600A

Manufacturer:
The Accu-CT ACTL-1250 series split-core current transformer (CT) offers revenue grade performance with a unique one-handed opening and closing mechanism
Part Number: ACTL-1250-xxx-RCM
*
Back to Previous Page
$157.00 ex GST
i h

Features:

  • Split-Core Current Transformer
  • Revenue Grade Accuracy
  • Excellent Linearity
  • Very Low Phase Angle Error

All CTs Are Not the Same!

Window Opening 1.25 Inch, 250 to 600 Rated Amps

The Accu-CT ACTL-1250 series split-core current transformer (CT) offers revenue grade performance with a unique one-handed opening and closing mechanism. The oval opening can handle a single 750 kcmil (MCM) conductor or two 400 kcmil (MCM) conductors.

  • Safe: burden resistor built-in, 333 mVac voltage output at rated full scale current, no shorting blocks needed
  • IEEE C57.13 and IEC 60044-1 accuracy: over full temperature range and down to 1% of rated current
  • Exceptionally low phase angle error: essential for accurate power and energy measurements
  • Glove-friendly: easy to open and install with one hand while wearing safety gloves
  • Approvals: UL listed, CE mark, RoHS
  • Best low-end accuracy of any split-core CT!

Models

  • List prices for quantity 1 to 30 pieces. Call for pricing on larger quantities.
  • Max Amps is the recommended maximum continuous current. See ACTL-1250 Maximum Amps for details.

Standard

ModelRated
Amps
ACTL-1250-250 250
ACTL-1250-400 400
ACTL-1250-600 600

Revenue Grade (call us for prices and availability)

ModelRated
Amps
ACTL-1250-250 Opt C0.6 250
ACTL-1250-400 Opt C0.6 400
ACTL-1250-600 Opt C0.6 600

Performance Graphs

  • Graphs show typical performance at 23°C, 60 Hz
  • Graph shows a positive phase angle when the output leads the primary current.

Safety Note

Warning: Hazardous Voltages - Only qualified personnel or licensed electricians should install the WattNode meter and current transformers.

Specifications

Accuracy

The accuracy specifications apply over the full operating temperature range (-30°C to 55°C) unless otherwise noted. Standard models are calibrated for optimum accuracy at 50-60 Hz.

The following accuracy specifications apply to the standard model (no options) or for Option C0.6; the specifications may vary for other options, so see the details on individual options for specifications.

Standard Accuracy

  • Accuracy: ±0.75% from 1% to 120% of rated primary current
  • Phase angle: ±0.50 degrees (30 minutes) from 1% to 120% of rated current
  • IEEE C57.13 accuracy: class 1.2 from 1% to 120% of rated current
  • IEC 60044-1 accuracy: class 1.0 from 1% to 120% of rated current

Revenue Grade Accuracy

With Option C0.6, the Accu-CT is calibrated and verified to meet IEEE/ANSI C57.13-2008 class 0.6 accuracy and IEC 60044-1 class 0.5 S accuracy and each CT is shipped with a certificate of calibration.

  • Accuracy: ±0.50% from 1% to 120% of rated primary current
  • Phase angle: ±0.25 degrees (15 minutes) from 1% to 120% of rated current
  • IEEE C57.13 accuracy: class 0.6 from 1% to 120% of rated current
  • IEC 60044-1 accuracy: class 0.5 and 0.5 S from 1% to 120% of rated current

Electrical

  • Primary rating: 250 to 600 amps nominal
  • Voltage and Measurement Category:
    • 600 Vac, CAT IV (service entrance) for pollution degree 2
    • 250 Vac, CAT III for pollution degree 3
  • Line frequency: 50 to 60 Hz nominal (available for up to 400 Hz)
  • Maximum continuous primary amps: 720 amps
  • Maximum primary conductor gauge: (see Wire Gauges)
    • One 750 kcmil THHN conductor (1.14 inch nominal diameter with insulation)
    • Two 350 kcmil THHN conductors. They must be in close contact to both fit.
  • Output: 333.33 mVac or 1.00 Vac (with Option 1V)
  • Output lead wires:
    • Standard length: 8 ft (2.4 m)
    • Gauge: #18 AWG
    • Type: MTW, UL 1015
    • Voltage: 600 Vac
    • Style: Two conductor: white and black, twisted
  • Internal Burden Resistance: see ACT-1250 Internal Burden Resistance

  • Width: 4.50 inches (114.0 mm)
  • Height: 3.30 inches (83.4 mm)
  • Thickness: 1.58 inches (40.2 mm)
  • Window: 1.83 x 1.26 inches (46.5 x 32.0 mm)
  • Weight: 13.9 oz (395 gm)
  • Material: PC/ABS

Miscellaneous

  • Operating temperature: -30°C to 75°C (–22°F to 167°F)
  • Altitude: up to 3000 m (9840 feet)
  • Operating Humidity: 5 to 95% relative humidity (RH)
  • Pollution Degree:
    • 2 (controlled environment) for CAT IV, 600 Vac
    • 3 (harsh environment) for CAT III, 250 Vac
  • Indoor Use: Suitable for indoor use.
  • Outdoor Use: Suitable for outdoor use when mounted in a NEMA 3R or 4 (IP 66) rated enclosure, provided the ambient temperature will not exceed 75°C (167°F).
  • UL listed: file number E363660 (XOBA), standard UL 2808
  • cUL listed (Canada): file number E363660 (XOBA7), standard CAN/CSA C22.2 No. 61010-1
  • CE mark: pending
  • RoHS
  • Assembled in USA
  • Label barcode: QR Code, "Model ; SerialNum"

Options

Opt C0.6

With Option C0.6, the Accu-CT meets IEEE/ANSI C57.13-2008 class 0.6 accuracy and IEC 60044-1 class 0.5 and class 0.5 S accuracy from -30°C to 55°C and from 1% to 120% of rated primary current (see CT Accuracy Standards).

  • Accuracy improves to ±0.5% from 1% to 120% of rated primary current from -30°C to 55°C.
  • Phase angle improves to ±0.25 degrees from 1% to 120% of rated primary current from -30°C to 55°C.
  • Includes a certificate of calibration
    • Order option C0.6,N if you need the C0.6 accuracy, but do not need a certificate of calibration.

Opt 50Hz

The ACT-1250 series of transformers are not available with a 50 Hz option, because it is not needed. The standard models (including Opt C0.6) meet the accuracy specifications over the full range from 50 to 60 Hz.

Opt FT

The Accu-CT can be ordered with custom lead lengths. For example, Opt FT=50 for 50 foot leads. We also sell extra lead wire to allow for field extension of the leads. Option FT does not affect the accuracy specifications.

Advanced Options

The Accu-CT advanced options are generally not useful when ordering the Accu-CT for use with a WattNode® meter, but may be useful for other applications.

Features:

  • Split-Core Current Transformer
  • Revenue Grade Accuracy
  • Excellent Linearity
  • Very Low Phase Angle Error

All CTs Are Not the Same!

Window Opening 1.25 Inch, 250 to 600 Rated Amps

The Accu-CT ACTL-1250 series split-core current transformer (CT) offers revenue grade performance with a unique one-handed opening and closing mechanism. The oval opening can handle a single 750 kcmil (MCM) conductor or two 400 kcmil (MCM) conductors.

  • Safe: burden resistor built-in, 333 mVac voltage output at rated full scale current, no shorting blocks needed
  • IEEE C57.13 and IEC 60044-1 accuracy: over full temperature range and down to 1% of rated current
  • Exceptionally low phase angle error: essential for accurate power and energy measurements
  • Glove-friendly: easy to open and install with one hand while wearing safety gloves
  • Approvals: UL listed, CE mark, RoHS
  • Best low-end accuracy of any split-core CT!

Models

  • List prices for quantity 1 to 30 pieces. Call for pricing on larger quantities.
  • Max Amps is the recommended maximum continuous current. See ACTL-1250 Maximum Amps for details.

Standard

ModelRated
Amps
ACTL-1250-250 250
ACTL-1250-400 400
ACTL-1250-600 600

Revenue Grade (call us for prices and availability)

ModelRated
Amps
ACTL-1250-250 Opt C0.6 250
ACTL-1250-400 Opt C0.6 400
ACTL-1250-600 Opt C0.6 600

Performance Graphs

  • Graphs show typical performance at 23°C, 60 Hz
  • Graph shows a positive phase angle when the output leads the primary current.

Safety Note

Warning: Hazardous Voltages - Only qualified personnel or licensed electricians should install the WattNode meter and current transformers.

Customers who bought this item also bought

VCP PAT - Air Differential Pressure Transmitters, 4-20mA - PAT 420D

$296.00 (ex gst)

HOBOnet Wireless Temp/RH Sensor (Battery Powered)

The HOBOnet Wireless Temperature and Relative Humidity Sensor provides a cost-effective and scalable solution for web-enabled monitoring of air temperature and humidity. HOBOnet Wireless Sensors communicate data directly to the RX Station or pass data through other wireless sensors back to the central station.
$546.00 (ex gst)

HOBOnet Manager

The HOBOnet Wireless Manager module is installed in an RX3000 station. Data is transmitted wirelessly from sensors across the network to the RX3000 station and then uploaded to HOBOlink, Onset’s innovative cloud-based software platform.
$453.00 (ex gst)