Technical Information - 0-500 VAC Voltage Sensor
|
Supply voltage |
2.0-3.8 VDC (3.0-3.8 VDC using power supply) * |
Current consumption |
0.2 μA (sleep mode), 0.7 μA (RTC sleep), 570 μA (MCU idle), 2.5 mA (MCU active), 5.5 mA (radio RX mode), 22.6 mA (radio TX mode) |
Operating temperature range (board circuitry and battery) |
-40°C to +85°C (-40°F to +185°F) |
Included battery |
Max temperature range |
-40° to +85°C (-40° to +185°F) |
Capacity |
1500 mAh |
Absolute Maximum Input Voltage |
600 VAC rms ** |
Response Time |
~1 Second |
Minimum Detection Voltage |
> 4 VAC rms |
Indeterminate Detection Region |
3 - 4 VAC rms |
Input Impedance |
2 MOhm |
Leaded wire specification |
2 Wires, 1 ft (12 in), Black (Line), White (Common), 18 AWG |
Datalogging |
Datalogs 2000 to 4000 readings if gateway connection is lost (non-volatile flash, persists through the power cycle): - 10-minute heartbeats = ~ 22 days - 2-hour heartbeats = ~ 266 days |
Wireless range |
1,200+ ft non-line-of-sight |
Security |
Encrypt-RF® (256-bit key exchange and AES-128 CTR) |
Weight |
4.7 ounces |
Enclosure rating |
NEMA 1, 2, 4, 4x, 12 and 13 rated, sealed and weather proof |
UL rating |
UL Listed to UL508-4x specifications (File E194432) |
Certification |
900 MHz product; FCC ID: ZTL-G2SC1 and IC: 9794A-G2SC1. 868 and 433 MHz product tested and found to comply with: EN 300 220-2 V3.1.1 (2017-02), EN 300 220-2 V3.1.1 (2017-02) and EN 60950 |